This measuring system is new! It is used to professionally to localize groups in building-bound low-voltage installations with a connection voltage of 230-400V-50Hz. This measuring system is specially designed for the installation sector. Without switching the groups on and off, it can be determined to which group a particular connection point is connected without the user of the premises getting harassed.
The system consists of 2 pulsers and 1 tracer and works on the basis of current collection. The Pulser is an ohmic load of 55 Watt that pulls a current with a unique behavior out of the net. This unique stream can only be found by the tracer. Both pulsers each have a separate current behavior, making it possible to determine from 2 connection points to which group they are connected.
This product is produced bij BSA B.V. an affiliated company of EMS B.V.
This product is distributed by MapTools: https://maptools.nl
For demonstrations and sales:
MapTools B.V.
Mr. M. Nijsen
Middelweg 10 C
6584 AH Molenhoek
Phone: +31 (0)24-348 32 25
http://www.maptools.nl
The Group detection measurement device can also be found on: https://groepenzoeker.nl
Standard delivery
The complete group search system consists of the following scope of delivery:
1 x Pulser 20, including power cord Schuko - IEC C13
1 x Pulser 22, including power cord Schuko - IEC C13
1 x Tracer (including 1 set of 4 1.5V AA penlite batteries)
1 x set of safety measuring leads CAT III - 600V / 10A or higher, consisting of 1 red and 1 black measuring lead with measuring pins on one side and a 4 mm safety plug on the other side
1 x Syncer
1 x connection cable M12 8 pole shielded male / female
1 x Probe
1 x storage case for all parts of the group search set
Pulser20 / Pulser 22
Table 1: Technical specifications Pulser
Dimensions | 255x91x80 mm (lxbxh) |
Weight | Ca. 0.95 kg |
Electrical connection | Fuced IEC C14 net entrance |
Supply voltage | 230V~ / 50Hz |
Maximum peak current | 3,1 A |
Power consumption | 55 W |
Fuse | 3,15AT (spare fuse is enclosed) |
EN-IEC 61010 category | CAT II – 300V |
IP classification | IP40 |
Operating temperature | -20…40°C |
Operating humidity | < 80%, non condensing |
Tracer
Tabel 2: Technical specifications Tracer
Dimenstions | 224x112x39 mm (lxbxh) |
Weight | Ca. 0.48 kg (incl. set alkaline batteries) |
Electrical connections | 2 x 4 mm test busses for direct contact measurements 1 x M12 8 pole interface for externe devices |
Supply | 4 x 1.5V AA battery (compatible with NiCd of NiMh rechargable AA batteries, which must be charged outside the measurement device) |
Fuse | 2 x Bussmann KTK 1/10 fuse 600Vac / 100mA / 100kA interrupt rating multimeter fuses build in for direct contact measurements. |
Galvanic separation for direct contact measurements | 3,75 kVrms / 1 minut |
EN-IEC 61010 category classification | CAT III – 600V |
IP classification | IP40 (excluded the connectors) |
Operating temperature | -20…40°C |
Operating humidity | < 80%, non condensing |
Syncer
Table 3: Technical specifications Syncer
Dimensions | 100x50x77 mm (lxbxh) |
Weight | Ca. 0.14 kg |
Connections | 1 x M12 8 pole interface for connection with the Tracer |
Supply voltage | 230V~ / 50Hz |
Power consumption | 2 W |
EN-IEC 61010 category classification | CAT II – 300V (supply side) |
Galvanic separation | 3,75 kVrms / 1 minut |
IP classification | IP40 |
Operating temperature | -20…40°C |
Operating humidity | < 80%, non condensing |
Probe
Table 4: Technical specifications Probe
Dimensions | Diameter 20 x 205 mm (excl. cable and M12 connector) |
Weight | Ca. 0.10 kg |
Connections | 1 x M12 8 pole connector for connection with the Tracer |
IP classification | IP40 |
Operating temperature | -20…40°C |
Operating humidity | < 80%, non condensing |